Set the fixed high limit (if required)
What is going on
Fixed high limit depends on the safety equipment installed and local codes. Vitorond 200 is factory set at 120 °C / 248 °F and can be lowered to 110 °C / 230 °F or 99 °C / 210 °F. Vitocrossal 300 is set at 99 °C / 210 °F. Once lowered, the fixed high limit cannot be reset to 120 °C / 248 °F.
Check in this order
- Disconnect power to the control and burner.
- Unclip the fuse box and swing it upwards.
- Turn the slotted screw on the rear of the fixed high limit until the slot points to 110 or 99 °C / 230 or 210 °F.
- Refit the fuse box.
Applies to: Vitorond 200 and Vitocrossal 300 boilers with Vitotronic 100 GC1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.