Viessmann · Boiler troubleshooting
Check cylinder burner assembly
What is going on
Inspect the cylinder burner mesh and replace the assembly if damaged.
Check in this order
- Undo the fitting on the gas supply pipe.
- Undo the boiler door screws and open the door.
- Remove side panels B and C.
- Check the wire mesh of cylinder burner assembly E for damage.
- Replace cylinder burner assembly E if required, following the burner replacement instructions.
Applies to: Vitocrossal 200 CM2 186 to 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.