Weil-McLain · Boiler troubleshooting
Removing the boiler from a shared common vent
What is going on
When this boiler leaves a common vent that other appliances still use, each remaining appliance must be checked by itself to confirm it still vents properly. Any venting fault found must be corrected to the National Fuel Gas Code.
Likely causes
- Undersized or pitched-wrong vent shared by other appliances
- Blockage, restriction, leakage or corrosion in the common vent
- Spillage from a remaining appliance when run alone with exhaust fans on
Check in this order
- Seal any unused openings in the common vent.
- Inspect the vent for proper size, horizontal pitch, blockage, restriction, leakage and corrosion.
- Close exterior doors and windows and doors to other spaces; turn on clothes dryers and non-vented gas appliances; run bathroom and range hood exhaust fans at maximum speed; close fireplace dampers. Do not run a summer exhaust fan.
- Run the remaining appliance alone with its thermostat set so it runs continuously.
- After 5 minutes of main burner operation, check for spillage at the draft diverter relief opening with a match or candle flame.
- If spillage occurs, correct the vent system before the install is complete.
- Return doors, windows, fans, fireplace dampers and other gas appliances to their original state.
Applies to: Boiler replacement on a shared common vent
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, pp. 10-11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.