Navien · Boiler troubleshooting

Connecting the boiler power supply

NCB700

What is going on

The boiler runs on a dedicated 110-120V AC supply with a breaker. It must not be connected to 220-240V. Only licensed professionals should make the connection.

Check in this order

  1. Do not connect power until all water and gas piping is complete and the boiler is filled with water.
  2. Use a dedicated 110-120V AC circuit with a breaker. Do not connect to 220-240V.
  3. The factory plug is 5 ft, 3-prong and rated 12 A. It plugs into any grounded outlet next to the boiler.
  4. If local code requires hardwiring, disconnect power, cut the cord about 2 in below the cabinet, and remove the four front cover screws.
  5. Splice the black (hot), white (neutral) and green (ground) wires to the supply with field-supplied twist-on connectors. Strip about 1/2 in of sheath first.
  6. Make sure the boiler is properly grounded. Do not use gas or water pipes as the ground, since plastic pipe or dielectric unions may stop proper grounding.
  7. Use a surge protector to protect the boiler from power surges.

Applies to: NCB700 electrical connection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.