Navien · Boiler troubleshooting
Connecting the boiler power supply
What is going on
The boiler runs on a dedicated 110-120V AC supply with a breaker. It must not be connected to 220-240V. Only licensed professionals should make the connection.
Check in this order
- Do not connect power until all water and gas piping is complete and the boiler is filled with water.
- Use a dedicated 110-120V AC circuit with a breaker. Do not connect to 220-240V.
- The factory plug is 5 ft, 3-prong and rated 12 A. It plugs into any grounded outlet next to the boiler.
- If local code requires hardwiring, disconnect power, cut the cord about 2 in below the cabinet, and remove the four front cover screws.
- Splice the black (hot), white (neutral) and green (ground) wires to the supply with field-supplied twist-on connectors. Strip about 1/2 in of sheath first.
- Make sure the boiler is properly grounded. Do not use gas or water pipes as the ground, since plastic pipe or dielectric unions may stop proper grounding.
- Use a surge protector to protect the boiler from power surges.
Applies to: NCB700 electrical connection
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.