Viessmann · Boiler troubleshooting

Enter coding level 1 and select a coding group

Vitodens 200-W B2HA

What is going on

Opens the coding menu on the Vitotronic control to change installer settings.

Check in this order

  1. Press OK and the second button shown in the manual together for about 4 seconds.
  2. Select Coding level 1.
  3. Select the group General, Boiler, DHW, Solar, Heating circuit 1/2/3, or All codes std device. The Solar group only appears when an SM1 solar control module is connected.
  4. Select the coding address.
  5. Select the value and confirm with OK.
  6. To reset all level 1 codes, choose Standard setting in Coding level 1. This also resets level 2 codes.

Applies to: Vitodens 200-W B2HA 80-100 Vitotronic 200-H

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA service instructions, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.