Viessmann · Boiler troubleshooting

Multi-boiler return temperature protection (circuit diagram 5)

Vitotronic 100 GC1

What is going on

Shunt pump and isolation valve arrangement for multi-boiler systems with manifold close to the boilers.

Likely causes

  • Return temperature falls below the required minimum value

Check in this order

  1. Check that sensor T2 switches the shunt pump on when the return is low.
  2. If the minimum return temperature is still not reached, reduce the boiler supply by at least 50% through sensor T1, the isolation valve, or the heating circuit controls.
  3. Size the shunt pump so bypassed water is about 30% of the boiler's total supply rate.
  4. On multi-boiler systems without the Vitotronic 333, the cascade and DHW tank control must be activated by a building automation system.

Applies to: Multi-boiler system with shunt pump per boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.