Viessmann · Boiler troubleshooting
Multi-boiler return temperature protection (circuit diagram 5)
What is going on
Shunt pump and isolation valve arrangement for multi-boiler systems with manifold close to the boilers.
Likely causes
- Return temperature falls below the required minimum value
Check in this order
- Check that sensor T2 switches the shunt pump on when the return is low.
- If the minimum return temperature is still not reached, reduce the boiler supply by at least 50% through sensor T1, the isolation valve, or the heating circuit controls.
- Size the shunt pump so bypassed water is about 30% of the boiler's total supply rate.
- On multi-boiler systems without the Vitotronic 333, the cascade and DHW tank control must be activated by a building automation system.
Applies to: Multi-boiler system with shunt pump per boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.