Central heating common components
What is going on
Parts the central heating loop needs around the boiler. Sizing and ratings are as listed in the manual.
Check in this order
- Size the expansion tank and charge it to 2 PSI (14 kPa) below the cold system pressure. Consult the tank maker for sizing when replacing it.
- Fit an air separator on the central heating supply side.
- Use the boiler control panel to read system pressure and temperature, which alternate on the display. An external gauge port is on the Primary-Secondary Heating Kit.
- Install a relief valve directly on the supply side of the boiler. Use the 30 PSI valve supplied with the boiler, or a 3/4 in valve in the 30 to 45 PSI range. The Primary-Secondary Heating Kit has a port for the central heating relief valve.
- Run the boiler only in a pressurized closed-loop heating system that is free of air and impurities.
- Install a water fill valve to hold proper pressure in the central heating circuit.
- Use a backflow preventer in the fill circuit where local code requires it.
- Install a dirt trap to protect the boiler from debris in the plumbing.
- Do not adjust or service the internal low water cut-off, which is a factory-installed pressure sensor type.
- If an external low water cut-off is required by local code, mount its probe above the minimum safe water level and wire it to the matching terminal on the boiler PC board.
Applies to: Central heating loop components
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.