Check CO2 setting at low and high fire

Vitodens 200-W

What is going on

Verify combustion by measuring CO2 and O2 at low fire and high fire using the actuator test.

Likely causes

  • Venting leak
  • Boiler set for wrong gas type
  • Readings more than 1% outside range

Check in this order

  1. Connect a flue gas analyzer to the test port at the boiler vent pipe adaptor.
  2. Open the gas shut-off valve, start the boiler and create a heat demand.
  3. Enter the service menu and open the actuator test.
  4. For low fire, select Base load OFF, then Base load ON appears and the burner runs at low fire.
  5. Measure CO2 and O2 and compare to the ranges.
  6. End with 'all actuators off' and record the values.
  7. For high fire, select Full load OFF, then Full load ON appears and the burner runs at high fire.
  8. Measure CO2 and O2 again and compare to the ranges.
  9. Exit the actuator test and record the values in the Maintenance Record on page 102.

Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.