Set up a variable speed boiler pump (0-10 Vdc output)
What is going on
Connect the control 0-10 Vdc output to the pump 0-10 Vdc input and set the pump voltages from the manual test screen.
Check in this order
- Connect the boiler 0-10 Vdc output to the 0-10 Vdc input of the pump.
- From the Contractor menu go to Diagnostics, then Manual Test Mode.
- Highlight FORCE RATE, select EDIT, use the arrows to set HIGH, then press SAVE.
- Adjust the pump voltage to the desired boiler delta T and press SAVE AS MAX VOLTS.
- Set Pump Volts back to AUTO to edit FORCE RATE again.
- Repeat for each FORCE RATE speed, including ignition speed. Ignition speed sets the voltage to the pump when the burner is not active.
Applies to: Variable speed boiler pump on 0-10 Vdc output
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.