Set up a variable speed boiler pump (0-10 Vdc output)

SVF 500/600 Series 1

What is going on

Connect the control 0-10 Vdc output to the pump 0-10 Vdc input and set the pump voltages from the manual test screen.

Check in this order

  1. Connect the boiler 0-10 Vdc output to the 0-10 Vdc input of the pump.
  2. From the Contractor menu go to Diagnostics, then Manual Test Mode.
  3. Highlight FORCE RATE, select EDIT, use the arrows to set HIGH, then press SAVE.
  4. Adjust the pump voltage to the desired boiler delta T and press SAVE AS MAX VOLTS.
  5. Set Pump Volts back to AUTO to edit FORCE RATE again.
  6. Repeat for each FORCE RATE speed, including ignition speed. Ignition speed sets the voltage to the pump when the burner is not active.

Applies to: Variable speed boiler pump on 0-10 Vdc output

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.