Viessmann · Boiler troubleshooting

Checking domestic hot water values

Versatronik 200

What is going on

DHW values show the measured tank temperatures, the current set values and the state of the heating request, charge pump and release.

Check in this order

  1. Read T-DHW Rated to confirm the hot water set temperature the control is using.
  2. Read T-DHW for the measured upper tank temperature.
  3. Read DHW-T B for the lower tank temperature. This matters for solar or solid fuel infeed and for charge-through operation.
  4. Read DHW require, DHW pump and DHW release to see whether hot water is requested, the charging pump is running and preparation is released.
  5. Read T-Circulation and Circulation pump if circulation temperature control is active.

Applies to: Domestic hot water preparation on the Versatronik 200

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 99. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.