Viessmann · Boiler troubleshooting

Wire the Hydrostat 3250-Plus burner control

Vitorond 100VR1

What is going on

Field wiring for the Hydrostat 3250-Plus control with a Beckett, Carlin or Riello burner. Power comes in on L1 and N to the high limit control.

Check in this order

  1. Disconnect power at the service switch before any wiring work.
  2. Connect incoming line hot (L1) to terminal L1 and neutral (N) to terminal L2 of the Hydrostat 3250-Plus.
  3. Secure the burner wiring harness to the boiler side panel with the two cable straps, coiled so there is no slack.
  4. For Beckett or Carlin burners, cut the burner harness to 6 in. to reach the burner junction box under the primary control.
  5. For Riello burners, the red wire is not used. Cap both ends with wire nuts, inside the high limit control and at the Riello sub-base.
  6. Run all 120 VAC wiring in flexible metal conduit and attach it to the 4x4 junction box on the burner, not to the cover mounting plate.
  7. Provide disconnect means, overload protection, electrical ground and low water cut-off as local codes require.

Applies to: Hydrostat 3250-Plus with Beckett, Carlin or Riello burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100, VR1 Installation and Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.