Wire the Hydrostat 3250-Plus burner control
What is going on
Field wiring for the Hydrostat 3250-Plus control with a Beckett, Carlin or Riello burner. Power comes in on L1 and N to the high limit control.
Check in this order
- Disconnect power at the service switch before any wiring work.
- Connect incoming line hot (L1) to terminal L1 and neutral (N) to terminal L2 of the Hydrostat 3250-Plus.
- Secure the burner wiring harness to the boiler side panel with the two cable straps, coiled so there is no slack.
- For Beckett or Carlin burners, cut the burner harness to 6 in. to reach the burner junction box under the primary control.
- For Riello burners, the red wire is not used. Cap both ends with wire nuts, inside the high limit control and at the Riello sub-base.
- Run all 120 VAC wiring in flexible metal conduit and attach it to the 4x4 junction box on the burner, not to the cover mounting plate.
- Provide disconnect means, overload protection, electrical ground and low water cut-off as local codes require.
Applies to: Hydrostat 3250-Plus with Beckett, Carlin or Riello burner
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100, VR1 Installation and Service Instructions, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.