Weil-McLain · Boiler troubleshooting
Reinstalling air silencer, gas valve and display after flue-side cleaning
What is going on
Final reassembly steps after the burner and heat exchanger have been cleaned. Gas valve steps apply only if the valve was removed.
Check in this order
- Press the air inlet silencer (item 1) onto the venturi air inlet and rotate it to the normal vertical position.
- If the gas valve was removed fit the flange and gas nipple to the valve inlet with 4 screws, with the gasket (item 6) between valve and flange.
- If the gas valve was removed slide the gas valve brackets down and fasten them to the top of the boiler with 3 screws.
- If the gas valve was removed reinstall the U-bolt and tighten it to hold the gas line in place.
- Put the silencer clip (item 2) back onto the air inlet silencer/venturi.
- Seat the display bracket tabs in the control panel slots, align the top screw holes and reinstall the screws.
- Perform a complete start-up and verification, then do a soap-suds leak test on all interior and exterior gas piping.
Applies to: 80/110/150/199 Series 3
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 152. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.