Viessmann · Boiler troubleshooting

Clearances and DHW piping requirements

Vitocrossal 300 CA3B Dual Fuel

What is going on

Keep at least 2 in. (51 mm) clearance from non-insulated hot water pipes to combustible construction. With suitable pipe insulation the clearance can be reduced to 0 in., following local gas codes. The DHW supply and return piping between the boiler and the Viessmann DHW tank must be at least 1¼ in. pipe. Non-Viessmann tanks need a check of coil pressure drop against the pump head. Viessmann recommends a temperature tempering valve in the DHW supply.

Likely causes

  • Failure to follow the DHW piping sizing can cause boiler short-cycling and inadequate DHW supply.

Check in this order

  1. Maintain 2 in. (51 mm) clearance from bare hot water pipes to combustible material, or insulate the pipe and follow local gas codes.
  2. Size DHW supply and return piping to at least 1¼ in.
  3. For non-Viessmann DHW tanks, calculate the tank coil pressure drop against the pump residual head.
  4. Verify the Viessmann DHW sensor operation with the tank manufacturer when a non-Viessmann tank is used.
  5. Install a temperature tempering valve in the DHW supply line.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 45. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.