Viessmann · Boiler troubleshooting
Clearances and DHW piping requirements
What is going on
Keep at least 2 in. (51 mm) clearance from non-insulated hot water pipes to combustible construction. With suitable pipe insulation the clearance can be reduced to 0 in., following local gas codes. The DHW supply and return piping between the boiler and the Viessmann DHW tank must be at least 1¼ in. pipe. Non-Viessmann tanks need a check of coil pressure drop against the pump head. Viessmann recommends a temperature tempering valve in the DHW supply.
Likely causes
- Failure to follow the DHW piping sizing can cause boiler short-cycling and inadequate DHW supply.
Check in this order
- Maintain 2 in. (51 mm) clearance from bare hot water pipes to combustible material, or insulate the pipe and follow local gas codes.
- Size DHW supply and return piping to at least 1¼ in.
- For non-Viessmann DHW tanks, calculate the tank coil pressure drop against the pump residual head.
- Verify the Viessmann DHW sensor operation with the tank manufacturer when a non-Viessmann tank is used.
- Install a temperature tempering valve in the DHW supply line.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.