Weil-McLain · Boiler troubleshooting

Clean the heat exchanger flue side interior

ECO Tec Series 3

What is going on

Remove the control circuit board first so water does not reach it. Use a strong light to confirm the flue ways are clear. Do not use any solvent on the exchanger. Use water only if a vacuum cannot clean it fully.

Likely causes

  • Accumulated deposits on the heating surfaces
  • Insulation pieces that fell into the exchanger
  • Lint or sediment blocking the flue ways

Check in this order

  1. Label and disconnect all connectors and harnesses from the circuit board, remove its four screws and snap-fit standoffs, and set the board aside.
  2. Use a strong light to check that the flue ways are clear and unobstructed.
  3. Use a vacuum to remove deposits and any insulation pieces from the heating surfaces. Do not use solvent.
  4. If the vacuum cannot clean it fully, place a shallow pan under the condensate tube connection.
  5. Loosen the condensate hose clamp and slide the trap off the drain connection (see page 63).
  6. Spray fresh water into the heat exchanger and tubes to remove sediment, collecting the water in the pan.

Applies to: ECO Tec Series 3 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 151. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.