Weil-McLain · Boiler troubleshooting
Clean the heat exchanger flue side interior
What is going on
Remove the control circuit board first so water does not reach it. Use a strong light to confirm the flue ways are clear. Do not use any solvent on the exchanger. Use water only if a vacuum cannot clean it fully.
Likely causes
- Accumulated deposits on the heating surfaces
- Insulation pieces that fell into the exchanger
- Lint or sediment blocking the flue ways
Check in this order
- Label and disconnect all connectors and harnesses from the circuit board, remove its four screws and snap-fit standoffs, and set the board aside.
- Use a strong light to check that the flue ways are clear and unobstructed.
- Use a vacuum to remove deposits and any insulation pieces from the heating surfaces. Do not use solvent.
- If the vacuum cannot clean it fully, place a shallow pan under the condensate tube connection.
- Loosen the condensate hose clamp and slide the trap off the drain connection (see page 63).
- Spray fresh water into the heat exchanger and tubes to remove sediment, collecting the water in the pan.
Applies to: ECO Tec Series 3 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 151. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.