Weil-McLain · Boiler troubleshooting

Ultra-399 propane conversion and start-up

Ultra Series 4

What is going on

The Ultra-399 is converted for propane by adjusting the gas valve throttle screw only; no orifice change. Requires a combustion analyzer.

Check in this order

  1. Before starting, turn the gas valve throttle screw clockwise 5 turns.
  2. Start the boiler following the startup procedure on page 40.
  3. Make slight throttle screw adjustments to reach CO2 of 10.2% with CO below 100 ppm air free. Let the analyzer reading stabilize before each change.
  4. When set correctly, fill in the propane conversion label and attach it to the boiler rating plate.

Applies to: Ultra-399 propane firing

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.