Rinnai · Boiler troubleshooting

DHW Recirculation Does Not Begin (Combi Only)

I-Series Plus

What is going on

Recirculation pump does not start.

Likely causes

  • Pump not on DHW_Pump terminal
  • Parameter 09 off
  • Recirculation plumbing type wrong (parameter 12)
  • Timer relay input wrong (parameter 13)
  • External timer wiring wrong or timer off
  • Recirculation OFF interval after use

Check in this order

  1. Confirm the recirculation pump is connected to the DHW_Pump terminal.
  2. Confirm parameter 09 is ON.
  3. Confirm the plumbing type is set per parameter 12.
  4. Confirm the timer relay input is set per parameter 13.
  5. Confirm wiring to the external timer is correct.
  6. Confirm the external timer is ON, if used.
  7. Wait out the recirculation OFF interval after use if it is normal.

Applies to: I-Series Plus combi boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 117. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.