DHW Recirculation Does Not Begin (Combi Only)
What is going on
Recirculation pump does not start.
Likely causes
- Pump not on DHW_Pump terminal
- Parameter 09 off
- Recirculation plumbing type wrong (parameter 12)
- Timer relay input wrong (parameter 13)
- External timer wiring wrong or timer off
- Recirculation OFF interval after use
Check in this order
- Confirm the recirculation pump is connected to the DHW_Pump terminal.
- Confirm parameter 09 is ON.
- Confirm the plumbing type is set per parameter 12.
- Confirm the timer relay input is set per parameter 13.
- Confirm wiring to the external timer is correct.
- Confirm the external timer is ON, if used.
- Wait out the recirculation OFF interval after use if it is normal.
Applies to: I-Series Plus combi boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 117. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.