Weil-McLain · Boiler troubleshooting
CGa pilot ignition sequence and lockout reset
What is going on
What the control does on a call for heat, so you know where it is stuck.
Likely causes
- Vent damper end switch not making
- Pilot not proving
- Propane lockout after failed tries
Check in this order
- On a call for heat the control may first just run the circulator to use stored heat before firing.
- Then the vent damper and circulator come on. Ignition only starts once the damper end switch makes.
- The control sparks and opens the pilot valve. Once flame is proven, spark stops and the main valve opens.
- Natural gas no pilot in 15 seconds = valve closes, wait 5 minutes, try again. This repeats with no limit.
- Propane no pilot in 15 seconds = wait 1 minute and try again, then 2 more tries with 5 minutes between. After that it locks out and needs a manual reset.
- Losing flame while running sends it back to pilot ignition. A limit trip closes the main valve but keeps the circulator and damper open.
- Manual reset on the fault screen press Enter, change NO to YES with the arrows, press Enter. The screen turns green when it clears (only if the problem is gone).
Applies to: CGa-25 to CGa-8, natural gas (config #15) and propane (config #5)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGa Series 4 Boiler Manual 550-100-223/0425, Operation - Spark-ignited pilot system, p.37; Errors and lockouts, p.64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.