Condensate drain installation
What is going on
Route condensate to a drain properly so the boiler does not shut down or the trap does not fail.
Likely causes
- Frozen or blocked drain line causes condensate to back up into the combustion chamber.
- Corrosive condensate attacks metal drains and sewer pipes.
Check in this order
- Do not run condensate lines outdoors.
- Do not use copper, steel or galvanized pipe for the condensate disposal system.
- Use the supplied 3/4 in I.D. corrugated hose to connect the trap to the drain. Extend it with poly or vinyl tubing if needed.
- Check local rules on whether condensate must be neutralized before disposal.
- If a condensate pump is needed, select one designed for condensate.
- Do not replace the factory condensate trap with another trap.
- Keep the trap secure to the bottom of the boiler with no strain on it.
- Keep the drain line away from areas that leaking condensate could damage.
Applies to: Condensate drain and trap
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand C95 & C140 installation & operating manual, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.