Weil-McLain · Boiler troubleshooting
Adjust boiler bypass valves (high water content systems)
What is going on
For high water content systems such as converted gravity systems. Not for radiant panel systems. Does not protect against high supply temperature.
Likely causes
- Low water temperature in the boiler, causing corrosion of sections or burners
Check in this order
- Start with valve 1 fully closed and valve 2 fully open.
- Slowly open valve 1 while closing valve 2.
- Adjust until the boiler gauge reads about 60°F higher than the system temperature gauge.
- Pause between adjustments so temperatures can level off.
- Install all components specified and adjust valves so the boiler never runs at low temperature.
Applies to: Boiler bypass method, Figure 20. Do not use on radiant panel systems.
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG/PEG Series 7 boiler manual, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.