Weil-McLain · Boiler troubleshooting

Adjust boiler bypass valves (high water content systems)

EG / PEG Series 7

What is going on

For high water content systems such as converted gravity systems. Not for radiant panel systems. Does not protect against high supply temperature.

Likely causes

  • Low water temperature in the boiler, causing corrosion of sections or burners

Check in this order

  1. Start with valve 1 fully closed and valve 2 fully open.
  2. Slowly open valve 1 while closing valve 2.
  3. Adjust until the boiler gauge reads about 60°F higher than the system temperature gauge.
  4. Pause between adjustments so temperatures can level off.
  5. Install all components specified and adjust valves so the boiler never runs at low temperature.

Applies to: Boiler bypass method, Figure 20. Do not use on radiant panel systems.

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.