Shut down the boiler and open the combustion chamber door for service
What is going on
Isolate the boiler and open the chamber before any cleaning or inspection.
Check in this order
- Make sure main power to the boiler, the heating system and all external controls is off, and take steps so nobody can switch it back on.
- Close the main oil supply valve near the burner and the one near the tank.
- Disconnect power to the boiler.
- Remove the front panel by lifting it up and out.
- Remove the two bolts on the combustion chamber door and open the door.
- Remove the flue gas turbulators if fitted.
- Remove the combustion chamber insert if fitted.
Applies to: VR1 40 to 63, 161 to 245
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 48. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.