Weil-McLain · Boiler troubleshooting
Owner and service maintenance schedule
What is going on
Owner checks daily, monthly and every 6 months; service technician annual start-up.
Check in this order
- Owner daily check boiler area, air openings, pressure/temperature gauge, and jacket door.
- Owner monthly check vent and air piping, relief valve, condensate drain, automatic air vents, and DHW temperature at fixtures.
- Owner every 6 months check boiler piping (gas and water) and operate the relief valve.
- Service technician complete the annual start-up checklist before the heating season.
Applies to: ECO Tec Series 3 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 138. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.