Weil-McLain · Boiler troubleshooting

Low-temperature system: primary/secondary bypass valve setup

CGi Series 5

What is going on

Preferred piping for radiant or converted gravity systems. Bypass valves 7a and 7b mix hot boiler outlet water with system return water so the boiler return stays at or above 130°F. Setting is done with the system cold.

Check in this order

  1. Set the valves while the system is cool, for the coldest expected water temperature (usually 60°F).
  2. Start with valve 7a fully closed and valve 7b fully open.
  3. Slowly open valve 7a while closing valve 7b until gauge 8 reads 130°F when gauge 4a reads 60°F.
  4. Confirm gauge 4b is installed on radiant systems so supply temperature to the tubing can be seen.
  5. If gauge 8 is not installed, adjust until the boiler-mounted temperature/pressure gauge reads at least 150°F with cold return water (about 60°F).

Applies to: CGi-25 to CGi-8 low-temperature systems, primary/secondary piping (Figures 19 and 20)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain CGi Series 5 boiler manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.