Viessmann · Boiler troubleshooting
System version 6: heating circuit, low temperature circuit and Vitorond with shunt pump
What is going on
Vitocrossal 300 as lead boiler and Vitorond 200 as lag boiler, controlled by a Viessmann control system with outdoor reset, modulating boiler water temperature and load-dependent sequential control. Return temperature control for the Vitorond uses the shunt pump and a closing isolation valve. Sensor T1 controls the isolation valve and sensor T2 switches the shunt pump. The return temperature control is either an accessory or must be provided on site.
Check in this order
- Connect at least 15% of the rated output to the lower return connection.
- Set T1 and T2 coding only on the low temperature boiler as marked in the coding table.
- Set the Vitocrossal 300 as permanent lead boiler using code 39 (value 1 to 4).
- Check the connection diagram on site for completeness and function, because it is only a recommendation.
- Wire single-phase and three-phase pumps through field-supplied motor contactors or starters.
Applies to: System version 6, Vitocrossal 300 with Vitorond 200 (125 kW to 500 kW)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 21-23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.