Vent damper installation requirements and steps

EG / PEG Series 7

What is going on

The boiler will not run without its damper on the models that require one. Only the listed dampers in Table 19 (page 85) are approved for these Universal Control Systems.

Check in this order

  1. Confirm the damper is required EG-30 to EG-65 natural gas, PEG-30 to PEG-65 steam and natural gas, must have a damper. EG-75 natural gas may have one.
  2. Use only an approved damper from Table 19.
  3. Install the plug (supplied in the damper carton for 4" to 8" dampers) in the hole in the damper blade.
  4. Mount the damper directly on top of the draft hood so it serves only that boiler. Do not add other connections.
  5. Mount horizontally or vertically per the damper maker's instructions, with the blade indicator visible to the user.
  6. Keep screws or rivets from interfering with blade rotation.
  7. Run the damper harness between the actuator and the knockout in the jacket top panel. Use strain relief connectors and locknuts at both ends.
  8. Keep the harness clear of hot surfaces.
  9. Put the harness plug warning label where it stays visible after installation.
  10. Plug the damper harness receptacle into the harness plug.
  11. Set the damper hold-open switch to Automatic Operation.

Applies to: EG-30 to EG-75 and PEG-30 to PEG-65 with vent damper

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 18-19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.