Combustion analysis and throttle adjustment
What is going on
Calibrate burner CO2 at maximum and minimum fire using a calibrated combustion analyzer.
Check in this order
- Use a calibrated analyzer that measures CO2 and CO, set for natural gas.
- Select 'Hi' in the System Test Menu and run for at least 5 minutes.
- Confirm gas line pressure stays within its min and max values.
- Insert the analyzer probe fully into the 1/2 inch flue test port in the exhaust vent adapter.
- Adjust the throttle screw with a 5/64 inch (2 mm) Allen key or flat screwdriver until CO2 is within Table 10.1 limits. Clockwise lowers CO2; counterclockwise raises it.
- Select 'Lo' and check that combustion stays smooth and CO2/CO fall within Table 10.2 limits. Do not adjust further at minimum fire; contact Glow Brand if out of range.
- Make sure the test port cap does not leak condensate when refitted, using approved sealant or Teflon tape.
Applies to: C95 & C140
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand C95 & C140 installation & operation manual, p. 52-53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.