Viessmann · Boiler troubleshooting

Check boiler water temperature sensor

Vitotronic 200

What is going on

Measure the boiler sensor resistance and compare it with the current boiler water temperature.

Check in this order

  1. Disconnect the sensor plug in the terminal compartment.
  2. Measure the resistance at terminals 1 and 2 of the plug.
  3. Compare the reading with the current boiler water temperature using the table.
  4. If the values differ significantly, check the installation.
  5. Replace the sensor if the installation is correct and the reading is still wrong.

Applies to: Boiler temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 service instructions, p. 69. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.