What is going on
Confirm the expansion tank type is correct, its fill level or charge is right, and it is sized for the system.
Likely causes
- Closed-type tank waterlogged
- Diaphragm or bladder tank too small or membrane damaged
- Frequent relief valve weeping
Check in this order
- If the relief valve weeps often, suspect a waterlogged or undersized tank.
- Closed-type tank install a tank fitting if none is present. Check fill level per the fitting manufacturer. If level is correct, check tank size. Replace with a larger tank if needed.
- Diaphragm or bladder tank check that the tank is large enough. Add tanks if undersized.
- Diaphragm or bladder tank if size is correct, remove it and check charge pressure (usually 12 psig for residential). If it will not hold pressure, replace the tank.
- Do not use automatic air vents on systems with closed-type tanks.
- Systems with diaphragm or bladder tanks need at least one automatic air vent, preferably on top of an air eliminator.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.