Annual startup: check expansion tank

SlimFit Series 2

What is going on

Confirm the expansion tank type is correct, its fill level or charge is right, and it is sized for the system.

Likely causes

  • Closed-type tank waterlogged
  • Diaphragm or bladder tank too small or membrane damaged
  • Frequent relief valve weeping

Check in this order

  1. If the relief valve weeps often, suspect a waterlogged or undersized tank.
  2. Closed-type tank install a tank fitting if none is present. Check fill level per the fitting manufacturer. If level is correct, check tank size. Replace with a larger tank if needed.
  3. Diaphragm or bladder tank check that the tank is large enough. Add tanks if undersized.
  4. Diaphragm or bladder tank if size is correct, remove it and check charge pressure (usually 12 psig for residential). If it will not hold pressure, replace the tank.
  5. Do not use automatic air vents on systems with closed-type tanks.
  6. Systems with diaphragm or bladder tanks need at least one automatic air vent, preferably on top of an air eliminator.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.