Weil-McLain · Boiler troubleshooting

Sidewall concentric termination: wall penetration sizes

Ultra Series 4

What is going on

Size the wall opening so the rain cap ribs seat on a solid stop. A thimble is preferred.

Check in this order

  1. For a 3 in termination, use a thimble with a 4-1/2 in hole, or cut a hole no larger than 4-3/4 in.
  2. For a 4 in termination, use a thimble with a 6 in hole, or cut a hole no larger than 6-1/4 in.
  3. Check that the wall is strong enough that the rain cap cannot be pushed in from outside.
  4. Secure the termination so the rain cap butts against the outside wall or outer thimble plate.

Applies to: 3 in and 4 in sidewall concentric termination

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 74. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.