Viessmann · Boiler troubleshooting

Heat-up time reduction after reduced operation

Vitodens 200-W

What is going on

When switching from reduced to standard room temperature, the boiler or supply temperature is temporarily raised.

Check in this order

  1. Set the additional temperature increase with FA (example 50 °C + 20% = 60 °C).
  2. Set the duration of the raised temperature with FB (example 60 minutes).

Applies to: Vitodens 200-W B2HA 80 to 100

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA Service Instructions, p. 91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.