Weil-McLain · Boiler troubleshooting
Zoning with circulators: four space heating zones
What is going on
Four space heating zones with no Indirect DHW, using thermostat inputs and circulator outputs. Shown for Heating Only models.
Check in this order
- Wire zone thermostats to J17-1/2, J17-4/5, J17-7/8 and J16-1/2.
- Wire circulators to Outputs 1 to 4 (2.2 A max each).
- During the WIZARD, choose the space heating system type that matches the heating system, or set it manually in the PRIORITY 2 menu of System Settings.
- Use the factory default settings for that system type, or change them if needed.
- Review the 120VAC output wiring on page 68 and the 24VAC input wiring on page 69.
Applies to: ECO Tec Series 3 Heating Only models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.