Set Wi-Fi client connection to a local access point
What is going on
Connect the gateway to a site wireless access point and make it the primary connection.
Check in this order
- On the Wi-Fi Client tab, set Wi-Fi Status to ENABLED.
- Enter the Wi-Fi SSID and Wi-Fi Password for the local access point.
- Enable DHCP, or set IP fields manually. If connected to a router, set the IP gateway to the router's IP address.
- Click Update Wi-Fi Settings, then click System Restart.
- Go to Common settings and set the Primary Connection to Wi-Fi Client.
Applies to: Gateway Wi-Fi client
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien Modbus/BACnet gateway installation and operation manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.