Viessmann · Boiler troubleshooting

Outdoor temperature sensor installation and wiring

Versatronik

What is going on

Mount the sensor where it will read outdoor air properly. Use shielded twisted pair if the cable runs near 120/240 VAC wiring, and ground only one end of the shield.

Check in this order

  1. Mount the sensor on the outside of the building, 2 to 2.5 m above ground, on the north or north-west wall.
  2. In multi-storey buildings, mount it in the upper half of the second storey.
  3. Keep the sensor away from windows, doors, air vents, balconies and gutters.
  4. Do not paint over the sensor housing.
  5. Wire the field cable to the terminals inside the sensor and run it through the strain relief at the bottom of the housing.
  6. Refit the sensor cover.
  7. Run the cable to the controller sub-base and connect it to terminals 5 and 6.
  8. Keep the cable away from high voltage conductors. If that is not possible, use stranded twisted shielded wire and ground only one end of the shield.

Applies to: Outdoor sensor on Versatronik COMO OT

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik COMO OT manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.