Example F - purpose and piping for variable-primary multi-boiler system

Evergreen Series 2

What is going on

Space heating with multiple zones, using primary piping and a variable speed system circulator. Each boiler has its own isolation valve (Item 17a) and bypass or differential pressure bypass valve (Item 17b or 38). The flow switch (Item 34) is recommended if flow could drop below the minimum in the sizing table. The motorized valve end switch should be wired into the proof-of-closure circuit. Figure 17 shows four boilers, and the layout can be adjusted for three to eight boilers.

Check in this order

  1. Pipe each boiler with an isolation valve, strainer on the return line, and boiler relief valve and discharge piping.
  2. Install a 2-way motorized valve with an end switch on each boiler (Item 17a) and wire the switch to proof of closure.
  3. Install a bypass valve or differential pressure bypass valve (Item 38) to prevent dead-heading the system pump.
  4. Install a flow switch (Item 34) if flow could drop below the minimum.
  5. Install system supply and return sensors (Item 30) within 6 pipe diameters, and no more than 3 feet, from the first and last boiler tees.

Applies to: Example F variable-primary piping, multiple EVG boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Evergreen Series 2 advanced manual, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.