Weil-McLain · Boiler troubleshooting

Inspect ignition electrode and flame sense rod

SVF Series 1

What is going on

Clean or replace the electrode and check the ignition wiring.

Likely causes

  • White oxide buildup on electrode or flame sense rod
  • Damaged gasket or harness

Check in this order

  1. Remove the ignition electrode from the combustion chamber.
  2. Clean oxides from the electrode and flame sense rod with steel wool.
  3. If the electrode cannot be cleaned, replace it.
  4. Replace the gasket if worn and reinstall it correctly positioned.
  5. Confirm the ground wire is on the spade connection.
  6. Inspect the flame sense harness and connections. Replace if needed.
  7. Check ignition cable resistance; a good cable reads 900 to 1000 ohms.
  8. Check ground continuity from the electrode to the ground terminal strip and replace bad ground wires.

Applies to: SVF 1500-3000. SVF 1500/2000 use a male spade for flame sense; SVF 2500/3000 use a female spade.

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 95. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.