Inspect ignition electrode and flame sense rod
What is going on
Clean or replace the electrode and check the ignition wiring.
Likely causes
- White oxide buildup on electrode or flame sense rod
- Damaged gasket or harness
Check in this order
- Remove the ignition electrode from the combustion chamber.
- Clean oxides from the electrode and flame sense rod with steel wool.
- If the electrode cannot be cleaned, replace it.
- Replace the gasket if worn and reinstall it correctly positioned.
- Confirm the ground wire is on the spade connection.
- Inspect the flame sense harness and connections. Replace if needed.
- Check ignition cable resistance; a good cable reads 900 to 1000 ohms.
- Check ground continuity from the electrode to the ground terminal strip and replace bad ground wires.
Applies to: SVF 1500-3000. SVF 1500/2000 use a male spade for flame sense; SVF 2500/3000 use a female spade.
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 95. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.