Weil-McLain · Boiler troubleshooting
Display blank but boiler is operating
What is going on
Display has lost communication with the control while the boiler still runs.
Likely causes
- Loose connection or pin misalignment at control plug P9, Pump/Com board P6 and J1, or display board
- Faulty display wire harness
- Display contrast set incorrectly
Check in this order
- Check for loose connections and pin alignment at control plug P9, Pump/Com board P6 + J1, and back of display board.
- Check continuity on the harness from display to control.
- Cycle power off and on and check operation.
- Replace the display module if the problem remains.
- If contrast is the issue, look at the screen from other angles, or adjust contrast (see display contrast tip).
Applies to: SlimFit 1000-2000 Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 2 boiler manual, p. 97. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.