Weil-McLain · Boiler troubleshooting
Massachusetts venting requirements for sidewall horizontal vent
What is going on
Applies to sidewall horizontally vented gas equipment in dwellings or residential buildings where the vent termination is under 7 ft above grade. Carbon monoxide detectors and a warning sign are required, and the local gas inspector checks them before approving the install. Exempt equipment includes units in a separate building or structure and equipment listed in NFPA 54 Chapter 10.
Check in this order
- Confirm the installation is a sidewall horizontal vent with the termination under 7 ft above grade.
- Confirm a hard-wired CO detector with alarm and battery backup is on the floor level where the boiler is installed.
- Confirm a battery or hard-wired CO detector with alarm is on each additional level served.
- If the requirements cannot be met at completion, a battery-operated CO detector with alarm must be installed in the interim, and the owner has 30 days to comply.
- Confirm CO detectors are listed to NFPA 720 and ANSI/UL 2034 and IAS certified.
- Confirm a metal or plastic sign at least 8 ft above grade, in line with the vent terminal, reads GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS. with letters at least 1/2 inch high.
- Leave the installation instructions, venting instructions and parts lists with the appliance.
Applies to: Sidewall horizontal vent installations in Massachusetts
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 Boiler Manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.