Weil-McLain · Boiler troubleshooting

Venting and combustion air setup requirements

SlimFit Series 2

What is going on

Each SlimFit needs its own vent. Vent and air piping must be airtight, follow the manual, and meet code. Use one of two methods: direct exhaust (room air) or direct vent (outside air piped in).

Likely causes

  • Common venting with another appliance
  • Leaking or obstructed vent or air piping
  • Contaminated combustion air
  • Insulated nonmetallic vent pipe

Check in this order

  1. Do not common vent a Category IV boiler or any other appliance. Each boiler gets its own vent.
  2. Check any remaining appliances on the same common vent per page 26 (not on these pages).
  3. Inspect the finished vent and air piping for airtightness and code compliance.
  4. Confirm all air openings are the correct size, unobstructed and free of airborne contaminants.
  5. Do not cover nonmetallic vent pipe with thermal insulation.
  6. Provide combustion air per the National Fuel Gas Code or the applicable CSA B149.1 sections, or local code.
  7. For direct exhaust take combustion air from the boiler room through openings, sized for all appliances sharing the space.
  8. For direct vent pipe combustion air from outside, not terminating where contaminated air can enter. Manifolding is shown in Figure 31 (page 36).
  9. Use only the vent and air materials listed in Figure 22 (page 25).

Applies to: SlimFit 1000-2000 Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.