Viessmann · Boiler troubleshooting

Leak testing gaskets and flue gas path

Vitocrossal 300 CA3B Dual Fuel

What is going on

Gaskets on the burner plate and flue gas components can be checked during operation with an inspection mirror. Condensate traces on the flue gas collector or thermal insulation also show a leak.

Check in this order

  1. Run the boiler and check the burner plate and flue gas routing gaskets with an inspection mirror.
  2. Remove thermal insulation parts if needed to see the gaskets.
  3. Use a dew point hygrometer at full load for gasket checks if available.
  4. Look for condensate on the flue gas collector or insulation.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 11, 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.