Viessmann · Boiler troubleshooting

Connect boiler activation contact (plug aVH, terminals 2 and 3)

Vitotronic 300

What is going on

Dry contact that controls preheat, isolation valve and modulation on external modulation setups.

Check in this order

  1. Disconnect power before wiring.
  2. Connect a dry contact to terminals 2 and 3 of plug aVH.
  3. With contact closed, preheat runs first for follow-up boilers (coding 2b). After preheat, minimum temperature holds and burner stages or modulation can be switched externally. Setpoint is chosen by coding 9b.
  4. With contact open, the isolation valve closes after about 5 minutes (coding 2C). External override of burner stages is not possible and no minimum temperature is held.
  5. On multi-boiler systems the lead boiler contact must be constantly closed.

Applies to: VD2/VD2A and CT3 with external modulation controller

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 41, 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.