Viessmann · Boiler troubleshooting

Gas static pressure check

Vitocrossal 300 CA3B

What is going on

Measure the static gas pressure at the boiler inlet with the burner off.

Check in this order

  1. Close the gas shut-off valve.
  2. Loosen the measuring connector screw A. Do not remove it.
  3. Connect a pressure gauge at measuring connector A.
  4. Open the gas shut-off valve.
  5. Measure static pressure. Maximum is 14 in. w.c.
  6. Record the reading in the maintenance record (p. 162).
  7. Make sure no open flame is in the room during the check.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B service instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.