Viessmann · Boiler troubleshooting
Gas static pressure check
What is going on
Measure the static gas pressure at the boiler inlet with the burner off.
Check in this order
- Close the gas shut-off valve.
- Loosen the measuring connector screw A. Do not remove it.
- Connect a pressure gauge at measuring connector A.
- Open the gas shut-off valve.
- Measure static pressure. Maximum is 14 in. w.c.
- Record the reading in the maintenance record (p. 162).
- Make sure no open flame is in the room during the check.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B service instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.