Adjust CO2 at full load (upper heating input)

Vitocrossal 300 CA3B Dual Fuel

What is going on

Set CO2 at full load first, then check partial load.

Check in this order

  1. Use button Y F to set the service display C to 100 (100%).
  2. Check the CO2 level at the flue pipe.
  3. If adjustment is needed, remove cap B and turn adjusting screw A in small steps with a 3 mm Allen key.
  4. Turning clockwise lowers CO2 (less gas); counter-clockwise raises CO2 (more gas).
  5. Record the value in the maintenance report on page 158.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 66. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.