Viessmann · Boiler troubleshooting
Piping layout: three zone circuits with low-loss header
What is going on
Boiler with DHW storage and three zone circuits. Total zone flow is above the boiler's maximum flow, so a low-loss header is required.
Check in this order
- Install a low-loss header. It is strongly recommended and sold as an accessory.
- Connect the DHW pump to output 21 and the boiler pump to output 20.
- Wire the thermostat for zone circuits 1, 2 and 3 as dry contacts.
- Connect zone circuit 1 to output 157.
- Connect zone circuits 2 and 3 to the outputs on the AM1 extension module (A1 and A2).
- Connect the outdoor sensor, DHW sensor and supply sensor.
Applies to: Vitodens 200-W B2HA/B2HB with AM1 extension module
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 42. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.