Piping layout: three zone circuits with low-loss header

Vitodens 200-W B2HAVitodens 200-W B2HB

What is going on

Boiler with DHW storage and three zone circuits. Total zone flow is above the boiler's maximum flow, so a low-loss header is required.

Check in this order

  1. Install a low-loss header. It is strongly recommended and sold as an accessory.
  2. Connect the DHW pump to output 21 and the boiler pump to output 20.
  3. Wire the thermostat for zone circuits 1, 2 and 3 as dry contacts.
  4. Connect zone circuit 1 to output 157.
  5. Connect zone circuits 2 and 3 to the outputs on the AM1 extension module (A1 and A2).
  6. Connect the outdoor sensor, DHW sensor and supply sensor.

Applies to: Vitodens 200-W B2HA/B2HB with AM1 extension module

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.