Weil-McLain · Boiler troubleshooting
Checking the limit control on a WTGO boiler
What is going on
The combination limit control (in the tankless heater plate, with low water cut-off) shuts off the burner on high water temperature but lets the circulator keep running while there is a call for heat. Maximum setting is 220°F.
Likely causes
- Limit set below the temperature the system needs
- Limit control or low water cut-off faulty
Check in this order
- With the burner running, turn the limit indicator below the actual boiler water temperature. The burner should stop and the circulator should keep running.
- Turn the limit back above the water temperature. The burner should light again.
- If the boiler has a low water cut-off, extra high limit or other field controls, test each one the way its maker says.
- Set the limit higher than the temperature the system needs, never above 220°F.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Check-out procedure p.30; System components p.33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.