Weil-McLain · Boiler troubleshooting

Checking the limit control on a WTGO boiler

Weil-McLain WTGO Series 4

What is going on

The combination limit control (in the tankless heater plate, with low water cut-off) shuts off the burner on high water temperature but lets the circulator keep running while there is a call for heat. Maximum setting is 220°F.

Likely causes

  • Limit set below the temperature the system needs
  • Limit control or low water cut-off faulty

Check in this order

  1. With the burner running, turn the limit indicator below the actual boiler water temperature. The burner should stop and the circulator should keep running.
  2. Turn the limit back above the water temperature. The burner should light again.
  3. If the boiler has a low water cut-off, extra high limit or other field controls, test each one the way its maker says.
  4. Set the limit higher than the temperature the system needs, never above 220°F.

Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Check-out procedure p.30; System components p.33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.