NTI · Boiler troubleshooting

Replace the main heat exchanger

TRX150

What is going on

Drain the boiler and disconnect the heating piping, relief valve pipe, air purger and return pipe before removing the heat exchanger.

Check in this order

  1. Drain the boiler and remove the combustion assembly.
  2. Remove the exhaust vent adapter on top of the boiler.
  3. Remove the two screws holding the CH relief valve pipe assembly to the top of the boiler.
  4. Remove the three clips on the automatic air purger, then remove the CH relief valve pipe.
  5. Disconnect the bottom of the heating supply pipe from the hydraulic group and from the air purger.
  6. Remove the automatic air purger from the heat exchanger.
  7. Disconnect the return pipe from the top of the pump, remove its clip and remove it from the boiler.
  8. Remove the condensate pipe as needed.
  9. Remove the six fixing screws from the heat exchanger. Remove the lateral panel if the left screws are hard to reach.
  10. Install the new heat exchanger, replace all sealing rings, and check for gas leaks.

Applies to: TRX150

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI TRX150 manual, p. 99-100. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.