What is going on
The SF-750 natural gas unit has no blower plate. The propane version needs the plate and gaskets shipped with the boiler.
Check in this order
- Turn off all power to the boiler.
- Disconnect the two wiring connectors on the blower.
- Disconnect the blower flange from the mixing tube flange and support the blower and gas train.
- Check that the plate reads "750 LP".
- Fit one gasket on each side of the blower plate, then position the blower.
- Start the nuts on the top two bolts, then the bottom two, without tearing the gasket.
- Torque the flange bolts to 15 N-m / 132 in-lbs / 11 ft-lbs, without over-tightening.
- Reconnect the two blower harnesses and reinstall the front door.
- Restore power, open the manual gas valve, check for leaks, then adjust combustion and run startup.
Applies to: SF-750 propane only
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 550/750 Series 3 boiler manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.