Viessmann · Boiler troubleshooting
Installing the control modules and programming unit
What is going on
Mount the control modules on the DIN rail inside the control panel. The layout is shown in the manual. Connect the modules with the supplied cables following the wiring overview on pages 58-59. The programming unit goes in the panel door.
Check in this order
- Mount the power supply module (A1), cascade electronic module (A2), power module (A3) and expansion module (A4) on the DIN rail in the layout shown.
- Connect the modules using the supplied connecting cables, following the wiring overview on pages 58 and 59.
- Cut a 305 x 129 mm opening in the control panel front door for the programming unit.
- If two programming units are used, keep 20 mm between them.
- Snap the frame into the opening.
- Insert the programming unit into the frame.
- Plug the programming unit connecting cable into the back of the programming unit and into the cascade electronic module (A2).
Applies to: Vitotronic 300-K MW1S control panel
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100/300-K installation and service instructions, p. 56-57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.