Weil-McLain · Boiler troubleshooting
ECO Tec S2 no space heat in warm weather (WWSD)
What is going on
With Warm Weather Shut Down on, the boiler will not fire for space heating when the outdoor temperature is above the WWSD setting. DHW still works.
Likely causes
- Outdoor temperature above the WWSD setting
- Outdoor sensor in the sun or near a heat source
Check in this order
- Check the WWSD setting under Boiler Settings (default OFF).
- Check the outdoor sensor reading. The sensor must be on an outside wall out of direct sun, with its wire outlet pointing down.
Applies to: ECO Tec 80/110/150/199 Series 2 heating only
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Sequence of operation p.74; Outdoor sensor p.63; Boiler settings p.17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.