Weil-McLain · Boiler troubleshooting
Boiler stays in standby and display shows WWSD
What is going on
Boiler will not fire because outdoor temperature is above the warm weather shut down setting. This is normal operation.
Likely causes
- Outdoor temperature is above the WWSD setting.
- Outdoor sensor is required for this function and must be installed.
Check in this order
- Read the outdoor temperature on the boiler information screen.
- Compare it with the WWSD TEMP setting in the contractor BOILER SETTINGS menu.
- If the boiler should fire, adjust WWSD TEMP to a suitable value.
- Confirm the outdoor sensor is installed and reading correctly.
Applies to: ECO Tec control with outdoor sensor
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 115. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.