Weil-McLain · Boiler troubleshooting

Boiler stays in standby and display shows WWSD

ECO Tec Series 3

What is going on

Boiler will not fire because outdoor temperature is above the warm weather shut down setting. This is normal operation.

Likely causes

  • Outdoor temperature is above the WWSD setting.
  • Outdoor sensor is required for this function and must be installed.

Check in this order

  1. Read the outdoor temperature on the boiler information screen.
  2. Compare it with the WWSD TEMP setting in the contractor BOILER SETTINGS menu.
  3. If the boiler should fire, adjust WWSD TEMP to a suitable value.
  4. Confirm the outdoor sensor is installed and reading correctly.

Applies to: ECO Tec control with outdoor sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 115. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.