Viessmann · Boiler troubleshooting
Wiring pumps that draw more than 2 FLA or are 3-phase/240V
What is going on
Pumps above 2 FLA, 208/460/575V three-phase pumps and 240V pumps must be switched through a field-supplied contactor or relay rated 120VAC 1A, fed from a power supply with disconnect and protection on a DIN rail. Pumps under 2 FLA can be wired directly.
Check in this order
- Fit a contactor or relay rated 120VAC 1A on the DIN rail.
- Feed the contactor from a power supply with disconnect and protection.
- Wire the pump through the contactor.
- For pumps under 2 FLA, wire the pump directly to the DIN rail.
Applies to: Pump wiring
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K Installation and Service, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.