Viessmann · Boiler troubleshooting
Combustion values out of range
What is going on
CO2 or O2 reading is outside the target range.
Likely causes
- Leak in the flue gas or combustion air system
- Contaminated or damaged burner gauze assembly
- High flue gas side pressure drop due to contamination
Check in this order
- Check the flue gas and combustion air system for leaks.
- Check the burner gauze assembly for damage or contamination.
- Check the pressure drop on the flue gas side of the boiler for contamination.
- Re-measure CO and CO2/O2 after correction and record results on page 95.
Applies to: Vitocrossal 200 CI2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.